Publiora

Menghubungkan ke Publiora...

Publiora

Partial Discharge Characterization based on Leakage Current Pulses Waveform for Contaminated Glass Insulator String

Othman, N. A.Piah, M. A. M.Adzis, Z.A. Al-geelani, Nasir
International Journal of Electrical and Computer Engineering (IJECE) (Sinta 1)Vol. 0 No. 01 April 2016
DOI10.11591/ijece.v6i2.pp835-843

Abstrak

This paper deals with the analysis of partial discharge (PD) occurrences based on leakage current (LC) pulses distribution under different level of contamination. In this work, laboratory based contamination performance tests are conducted on four units of glass insulator string stacked in I-position. Results show that PD can be characterized (according to their occurrence with respect to the AC supply) as follows: corona discharge occurring dominantly in lightly contaminated insulators, surface discharge occurring dominantly in medium contaminated insulators and finally internal discharge occurring dominantly in heavily contaminated insulators. The ability to distinguish the type of PDs from the LC waveform could be used to monitor and predict the condition of the insulator. The outcome can be incorporated in a conditioning monitoring system.

Kata Kunci

Electrical (Power)Partial dischargeLeakage currentGlass insulator string

Cari jurnal yang tepat untuk naskah Anda

MatchMind AI mencocokkan abstrak naskah Anda dengan ribuan jurnal terakreditasi dan menampilkan rekomendasi terbaik beserta alasannya.

Coba MatchMind

Lihat profil lengkap jurnal ini

Waktu review, biaya APC, statistik sitasi, indeksasi Scopus, dan banyak lagi.

Buka International Journal of Electrical and Computer Engineering (IJECE)

Artikel ini juga tersedia di situs resmi jurnal.

Partial Discharge Characterization based on Leakage Current Pulses Waveform for Contaminated Glass Insulator String | International Journal of Electrical and Computer Engineering (IJECE) | Publiora