The use of Markov Chain method to determine spare transformer number and location

Marbun, Musa PartahiSinisuka, Ngapuli IrmeaHariyanto, Nanang
International Journal of Electrical and Computer Engineering (IJECE) (Sinta 1)Vol. 0 No. 01 Februari 2019
DOI10.11591/ijece.v9i1.pp1-13

Abstrak

The purpose of this study is to develop a method to determine spare transformer number and location. Using Markov Chain method, state transition model and steady state probability was used on each 500-kV substation in order to analyze the effect of spare number and location variation with the reliability changes.  To give an actual result of the case study, calculation of spare transformer number and location on 500/150 kV transformers in Java Bali System was analyzed. The steady state probability results will vary depending on the number of spare transformer, these results can then be used to assess the spare transformer needed. The variation of spare transformer location can be used to analyze the best possible location of the spare in order to satisfy the reliability required. The methodology presented shows an integrated calculation for determining the spare transformer number and location.

Kata Kunci

Electrical (Power)Asset Managementspare locationspare numbertransformermarkov chainprobability steady state

Cari jurnal yang tepat untuk naskah Anda

MatchMind AI mencocokkan abstrak naskah Anda dengan ribuan jurnal terakreditasi dan menampilkan rekomendasi terbaik beserta alasannya.

Coba MatchMind

Lihat profil lengkap jurnal ini

Waktu review, biaya APC, statistik sitasi, indeksasi Scopus, dan banyak lagi.

Buka International Journal of Electrical and Computer Engineering (IJECE)

Artikel ini juga tersedia di situs resmi jurnal.

The use of Markov Chain method to determine spare transformer number and location | International Journal of Electrical and Computer Engineering (IJECE) | Publiora