An Analysis of Harmonic and Interharmonic Contribution of Electric Arc Furnace by Using Periodogram
Abstrak
Fast and accurate detection of the harmonic and interharmonic contribution of electric arc furnace (EAF) is crucial in identifying and to mitigate the undesired effects to the system. In this paper, periodogram, a fast and accurate technique is introduced for the analysis of the contribution. Based on a rule-based classifier and the threshold settings that referred to the IEEE Standard 1159 2009, the analysis of the harmonic and interharmonic contribution of EAF are carried out successfully. Moreover, the impact of contribution is measured using total harmonic distortion (THD) and total non-harmonic distortion (TnHD). In addition, periodogram also gives 100 percent correct detection and able to analyze the contribution impact. It is proven that the proposed method is accurate, fast and cost efficient for analyzing the impact of harmonic and interharmonic of EAF.